| UNDERWRITERS LABORATORIES | APPLIANCE WIRING MATERIAL | ||||
| Subj.758 | Section 2 | Page 2733 | Issued:1975-06-23 |
| Revised:2008-05-27 | |||
| Style 2733 | Jacketed Cord. | |
| Rating | 105 deg C, 600 Vac, Horizontal flame. |
| Insulation | Labeled style 1015 |
| Assembly | Two to seven conductors cabled together. Length of lay not specified. Fillers optional. Maximum diameter of cable assembly under jacket is .350 inches. |
| Jacket | PVC, 15 mils min average, 12 mils minimum at any point. |
| Standard | Appliance Wiring Material UL 758. |
| Marking | General. |
| Use | Internal wiring of electric fans. |
3
| UNDERWRITERS LABORATORIES | APPLIANCE WIRING MATERIAL | ||||
| Subj.758 | Section 2 | Page 2516 | Issued:1970-10-21 |
| Revised:2008-05-27 | |||
| Style 2516 | Jacketed Cord. | |
| Rating | 105 deg C, 600 Vac, Cable flame. |
| Conductor | 40 AWG min. solid or stranded round, tinned or bare copper. |
| Insulation | Labeled or complying with Manufacturer's ConductorsAWM Procedure |
| Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
| Shield | Optional. |
| Covering | (Optional) A 6 mil or heavier PVC covering may be extruded over the conductor assembly. |
| Jacket | PVC |
| major dia in inches of 0.425 or less | 45 mils min average | 36 mils minimum at any point |
| 0.426-0.700 dia | 60avg | 48 min |
| 0.701-1.500 dia | 8Oavg | 64 min |
| Standard | Appliance Wiring Material UL 758. |
| Marking | General. |
| Use | External interconnect of electronic equipment. |
4
2733 是最多能做7C 嗎。
5
直接登錄UL網(wǎng)站去下載就好了。
6
這資料我也需要,麻煩分享一下