1
| 計(jì)算鋁線電壓降(220V負(fù)載為電阻) | ||
| 截面mm² | 負(fù)荷矩 | 電壓損 |
| 2.5 | 20KWm (標(biāo)準(zhǔn)值) | 1% |
| 4 | 4/2.5=1.6 1.6*20kwm=32kwm | 1% |
| 6 | 6/2.5=2.4 2.4*20kwm=48kwm | 1% |
| 10 | 10/2.5=4 4*20kwm=80kwm | 1% |
| 16 | 16/2.5=6.4 6.4*20kwm=128kwm | 1% |
| 25 | 25/2.5=10 10*20kwm=200kwm | 1% |
| 35 | 35/2.5=14 14*20kwm=280kwm | 1% |
| 50 | 50/2.5=20 20*20kwm=400kwm | 1% |
| 70 | 70/2.5=28 28*20kwm=560kwm | 1% |
| 95 | 95/2.5=38 38*20kwm=760kwm | 1% |
| 120 | 120/2.5=48 48*20kwm=960kwm | 1% |
| 150 | 150/2.5=60 60*20kwm=1200kwm | 1% |
| 負(fù)荷矩=導(dǎo)線長度*負(fù)荷功率= KWm | ||
| 例如:鋁導(dǎo)線4mm²40m長供220V、1KW電爐兩臺(tái)估算電壓降 | ||
| 1.計(jì)算負(fù)荷矩:2KW*40m=80kwm | ||
| 2. 4mm²電壓損1%時(shí)負(fù)荷矩為32kwm | ||
| 3.線路電壓損為:80kwm/32kwm=2.5% | ||