2
| UNDERWRITERS LABORATORIES | APPLIANCE WIRING MATERIAL | ||||
| Subj.758 | Section 1 | Page 1015 | Issued:1959-05-01 |
| Revised:2008-05-27 |
| Style 1015 | Insulated Wire. | |
| Rating | 80, 90, 105 deg C, 600 Vac, 750 Vdc, Horizontal flame, Oil Resistant 60 deg C or 80 deg C (optional) |
| Conductor | 30 AWG - 2000 kcmil Solid or Stranded Round, tinned or bare copper. |
| Insulation | PVC |
| 30-9 AWG conductor size | 30 mils min average | 27 mils minimum at any point |
| 8-7 AWG | 45 avg | 40 min |
| 6-2 AWG | 60 avg | 54 min |
| 1-4/0 AWG | 80 avg | 72 min |
| 250-500 kcmil | 95 avg | 86 min |
| 550-1000 kcmil | 110 avg | 99 min |
| 1100-2000 kcmil | 125 avg | 112 min |
| Standard | Appliance Wiring Material UL 758. |
| Marking | General. |